Inverters need a set battery voltage, usually 12, 24 or 48 V, and the battery bank has to match it. Wiring batteries in series adds up the volts; wiring strings in parallel adds up the amp hours. Either way the energy in kWh is simply all the batteries added together. This calculator works out the bank and sketches how it is wired.
Series, parallel and series parallel
- Series: the plus of one battery goes to the minus of the next. Four 12 V 100 Ah batteries in series make 48 V 100 Ah.
- Parallel: plus to plus and minus to minus. Two 12 V 100 Ah batteries in parallel make 12 V 200 Ah.
- Series parallel: several series strings joined in parallel. Eight 12 V 100 Ah batteries as two strings of four make 48 V 200 Ah, about 9.6 kWh.
Use the "Set series count" button to see how many of your batteries make up one string for a 12, 24 or 48 V inverter.
How the sum works
Bank volts = one battery's volts × the number in series. Bank amp hours = one battery's amp hours × the number of strings. Energy in kWh = volts × amp hours ÷ 1,000. Usable energy takes about 90% for lithium and 50% for lead acid, the depth most installers plan for to give a long life.
Good wiring practice
- Use identical batteries: same make, model, capacity, age and state of charge. A weak battery in a string drags down the others.
- Connect the inverter's cables to opposite corners of a parallel bank (plus at one end, minus at the other) or use bus bars, so every string carries the same current.
- Use equal length links of the right size, a fuse or breaker close to the battery, and torque the terminals to the maker's figure.
- Modern 48 V lithium modules usually go in parallel with a communication cable to the inverter, set up by the installer.