The label on a battery gives volts and amp hours; what you want to know is how long it keeps the lights or the router going. Volts times amp hours gives watt hours, the energy in the battery. Take off the reserve that protects it, the inverter's losses and, for lead acid, the capacity it loses when the current is high, and divide by the load.
How to use it
- Pick the battery voltage and enter the amp hours from the label. For a bank, set how many there are and how they are wired: in parallel the amp hours add up, in series the volts do.
- Pick the chemistry. The reserve sets itself to 10% for lithium and 50% for lead acid; slide it if your inverter cuts off at a different point.
- Enter the load in watts. Choose "an inverter" for 230 V appliances and "direct DC" for 12 V lights, routers or fridges wired straight to the battery.
How the sum works
Energy = volts × amp hours. A 51.2 V 100 Ah lithium battery holds 5,120 Wh; a 12 V 100 Ah lead acid battery holds 1,200 Wh. Usable energy takes off the reserve. The current is the load divided by the battery voltage and the inverter efficiency (about 90%).
Lead acid batteries are rated over 20 hours. Drain them faster and they deliver less than the label (the Peukert effect), so the calculator reduces the capacity at high currents: a little for AGM and gel, more for flooded batteries. Lithium hardly loses any. The discharge rate in C is the current divided by the amp hours: 0.2 C on a 100 Ah battery is 20 A.
Worked examples
- A 51.2 V 100 Ah lithium battery running 500 W through an inverter: 5,120 Wh, 4,608 Wh usable, just over 8 hours.
- A 12 V 100 Ah AGM battery running a 300 W load through an inverter: 600 Wh usable, but at 28 A it loses some capacity, so about 1 hour 25 minutes.
- A 12.8 V 100 Ah lithium battery running a 15 W router directly on 12 V: about 77 hours, more than three days.