Get backup quotes

Free calculator · TL-02

Battery runtime calculator: how long will my battery last?

Enter the battery's voltage and amp hours and the load in watts. The meter shows how long it runs, the current it draws and how hard the battery is working.

Battery runtime calculatorTL-02 · battery and load in, hours out
TL-02

01The battery

Wired in
Battery type
10%

02The load

Powered through
Runtime0
Battery bank
-
Usable energy
-
Current from the battery
-
Discharge rate
-
High current loss
-

A planning estimate from rules of thumb, not a design. An installer or electrician checks the real loads, cables and equipment before anything is bought or fitted.

The label on a battery gives volts and amp hours; what you want to know is how long it keeps the lights or the router going. Volts times amp hours gives watt hours, the energy in the battery. Take off the reserve that protects it, the inverter's losses and, for lead acid, the capacity it loses when the current is high, and divide by the load.

How to use it

  • Pick the battery voltage and enter the amp hours from the label. For a bank, set how many there are and how they are wired: in parallel the amp hours add up, in series the volts do.
  • Pick the chemistry. The reserve sets itself to 10% for lithium and 50% for lead acid; slide it if your inverter cuts off at a different point.
  • Enter the load in watts. Choose "an inverter" for 230 V appliances and "direct DC" for 12 V lights, routers or fridges wired straight to the battery.

How the sum works

Energy = volts × amp hours. A 51.2 V 100 Ah lithium battery holds 5,120 Wh; a 12 V 100 Ah lead acid battery holds 1,200 Wh. Usable energy takes off the reserve. The current is the load divided by the battery voltage and the inverter efficiency (about 90%).

Lead acid batteries are rated over 20 hours. Drain them faster and they deliver less than the label (the Peukert effect), so the calculator reduces the capacity at high currents: a little for AGM and gel, more for flooded batteries. Lithium hardly loses any. The discharge rate in C is the current divided by the amp hours: 0.2 C on a 100 Ah battery is 20 A.

Worked examples

  • A 51.2 V 100 Ah lithium battery running 500 W through an inverter: 5,120 Wh, 4,608 Wh usable, just over 8 hours.
  • A 12 V 100 Ah AGM battery running a 300 W load through an inverter: 600 Wh usable, but at 28 A it loses some capacity, so about 1 hour 25 minutes.
  • A 12.8 V 100 Ah lithium battery running a 15 W router directly on 12 V: about 77 hours, more than three days.

Frequently asked questions

How long will a 100Ah battery last?
It depends on the voltage and the load. A 12 V 100 Ah lithium battery holds about 1.28 kWh, so it runs a 100 W load for about 10 hours through an inverter. A 12 V 100 Ah lead acid battery used to half its capacity runs the same load for about 5 hours.
How long does a 5kWh battery last?
Through an inverter, a 5.12 kWh lithium battery runs 500 W (lights, wifi, a TV and a fridge) for about 8 hours, and 1,000 W for about 4 hours. The fridge does not draw full power all the time, so real homes often get more.
Why does my battery run out sooner than the calculator says?
Old batteries hold less than the label, especially lead acid after a few years. Cold weather, loads that are bigger than you think (check the inverter's display), and a high reserve setting in the inverter all shorten the runtime. A battery capacity test by an installer shows what is left.

More calculators

Free quote request

Get quotes for this system

Plan it the way an installer would on a site visit: switch on what must keep running and for how long, or describe the system and the job, and say how to reach you. Installers, electricians and suppliers who work in your area quote you directly.

Backup plan & quote requestFREE · NO OBLIGATION · BT-01 · LiFePO4
Nº 029928

01The job

02How many (optional, it helps the quote)

TALLY · HOW MANY

Running
-
Energy
-
Suggests
-
Estimate
-

A rule of thumb from published prices, not a quote.

03When

04Request list (optional)

  1. 01
  2. 02
Up to 12 lines: inverters, batteries, UPS units, lights or work.
Needs and options

05Your details

Free and no obligation. By sending you agree that we may share your request with suitable installers, electricians and suppliers. See our privacy policy.

Get free battery backup quotes