Battery cable size and fuse calculator

The cable between the battery and the inverter carries the biggest current in the system. Enter the inverter's watts, the battery voltage and the cable length to see the current, the fuse and the cable size.

Battery cable and fuse calculatorTL-06 · DC side only, battery to inverter
TL-06

01The inverter

The rated watts, not the surge figure.
Battery voltage

02The cable run

Battery to inverter. The sum counts both the plus and minus cables.
Allowed voltage drop
Cable size (copper)0
Fuse or DC breaker
-
DC current at low battery
-
Size set by
-
Voltage drop
-
Heat lost in the cable
-

A planning estimate from rules of thumb, not a design. An installer or electrician checks the real loads, cables and equipment before anything is bought or fitted.

A 5,000 W inverter on a 48 V battery draws over 100 A; on 12 V it would draw over 450 A. Cable that is too thin heats up, wastes power and drops the voltage so the inverter alarms or cuts out early. A fuse that is too big does not protect the cable. This calculator gives planning figures for the DC side only. The 230 V side, the earthing and the Certificate of Compliance are the electrician's work under SANS 10142-1.

How to use it

  • Enter the inverter's continuous output in watts and its efficiency (90% if you do not know it).
  • Choose the battery voltage and enter the cable length from the battery to the inverter, one way.
  • Choose the voltage drop you allow: 1% to 2% is usual for battery cables, 3% at most.

How the sum works

The current is worked out at a low battery voltage (11 V, 22 V or 46 V), when it is highest: watts ÷ (low voltage × efficiency). The fuse is the next common size above 1.25 times that current. The cable must be rated for at least the fuse, and thick enough that the voltage drop over the plus and minus cables stays within your limit: area = 2 × length × current × 0.0175 ÷ allowed volts, using copper's resistance. The bigger of the two wins.

The current ratings used are conservative figures for single flexible copper battery cable in open air over short runs. Cable in conduit, bundled together or in a hot space must be bigger; the cable maker's tables and the installer have the final say.

Common results

InverterBatteryCurrentFuseCable at 1.5 m
1,000 W12 V101 A150 A50 mm²
3,000 W24 V152 A200 A70 mm²
5,000 W48 V121 A160 A50 mm²
8,000 W48 V193 A250 A95 mm²

From this calculator at 90% efficiency and 2% drop. Many inverters come with their own cable and fuse sizes in the manual: use those when they are bigger.

Frequently asked questions

What size cable for a 5kVA inverter?
On a 48 V battery, a 5 kVA inverter draws up to about 120 A, which points to about 50 mm² copper cable with a 160 A fuse for a short run. Check the inverter manual, which often gives the cable and fuse sizes, and ask the installer to confirm.
Do I need a fuse between the battery and the inverter?
Yes. A battery can deliver thousands of amps into a short circuit, enough to melt cable and start a fire. A DC rated fuse or breaker close to the battery's plus terminal protects the cable. Many lithium batteries have a built in breaker, but most installers still fit one in the cable.
Can I install the battery cables myself?
Plug in systems like inverter trolleys and power stations need no wiring. A fixed inverter connected to your DB board must be installed by a registered electrician, who issues a Certificate of Compliance. See inverter installation.

More calculators

Free quote request

Get quotes for this system

Plan it the way an installer would on a site visit: switch on what must keep running and for how long, or describe the system and the job, and say how to reach you. Installers, electricians and suppliers who work in your area quote you directly.

Backup plan & quote requestFREE · NO OBLIGATION · BK-06 · 1 day
Nº 047350

01The job

02The system and the job (optional, it helps the quote)

JOB TICKET · THE WIRING

Running
-
Energy
-
Suggests
-
Estimate
-

A rule of thumb from published prices, not a quote.

03When

04Request list (optional)

  1. 01
  2. 02
Up to 12 lines: inverters, batteries, UPS units, lights or work.
Needs and options

05Your details

Free and no obligation. By sending you agree that we may share your request with suitable installers, electricians and suppliers. See our privacy policy.

Get free battery backup quotes