A 5,000 W inverter on a 48 V battery draws over 100 A; on 12 V it would draw over 450 A. Cable that is too thin heats up, wastes power and drops the voltage so the inverter alarms or cuts out early. A fuse that is too big does not protect the cable. This calculator gives planning figures for the DC side only. The 230 V side, the earthing and the Certificate of Compliance are the electrician's work under SANS 10142-1.
How to use it
- Enter the inverter's continuous output in watts and its efficiency (90% if you do not know it).
- Choose the battery voltage and enter the cable length from the battery to the inverter, one way.
- Choose the voltage drop you allow: 1% to 2% is usual for battery cables, 3% at most.
How the sum works
The current is worked out at a low battery voltage (11 V, 22 V or 46 V), when it is highest: watts ÷ (low voltage × efficiency). The fuse is the next common size above 1.25 times that current. The cable must be rated for at least the fuse, and thick enough that the voltage drop over the plus and minus cables stays within your limit: area = 2 × length × current × 0.0175 ÷ allowed volts, using copper's resistance. The bigger of the two wins.
The current ratings used are conservative figures for single flexible copper battery cable in open air over short runs. Cable in conduit, bundled together or in a hot space must be bigger; the cable maker's tables and the installer have the final say.
Common results
| Inverter | Battery | Current | Fuse | Cable at 1.5 m |
|---|---|---|---|---|
| 1,000 W | 12 V | 101 A | 150 A | 50 mm² |
| 3,000 W | 24 V | 152 A | 200 A | 70 mm² |
| 5,000 W | 48 V | 121 A | 160 A | 50 mm² |
| 8,000 W | 48 V | 193 A | 250 A | 95 mm² |
From this calculator at 90% efficiency and 2% drop. Many inverters come with their own cable and fuse sizes in the manual: use those when they are bigger.