When outages come back to back, the battery may not be full when the next one starts. How fast it refills depends on the charge current the inverter allows from the grid, and, with solar, on the panels, the sun where you live and what the house uses during the day. This calculator checks both.
How to use it
- Enter the battery size in kWh (a 48 V 100 Ah lithium module is 5.12 kWh) and the charge level at the end of an outage, often 20% to 40%.
- Enter the grid charge current set in the inverter. Many 5 kVA inverters allow 50 to 100 A at 48 V, but installers often set it lower to protect the batteries or the supply.
- For solar, enter the panel size and count, pick the sun where you live, and the watts the house uses in daylight (fridge, wifi, TV, a pool pump if it is on the system).
How the sum works
Energy to put back = battery kWh × the percentage to refill, plus charging losses (about 5% for lithium, 20% for lead acid). Grid charge time = that energy ÷ (charge current × battery voltage).
Solar per day = panel watts × panel count × full sun hours × 0.75. The 0.75 covers heat, dust, cable and inverter losses and panels that do not face the sun perfectly. The daytime load over about 9 daylight hours comes off the top; what is left charges the battery. Full sun hours are a yearly average, so winter and cloudy days give much less.
A worked example
A 10.24 kWh lithium bank used down to 20% needs about 8.6 kWh back. At 50 A on 48 V (2.4 kW) that takes about 3 hours 35 minutes from the grid. Six 550 W panels in Gauteng make about 13.6 kWh on a clear day; after a 300 W daytime load (about 2.7 kWh) there are about 10.9 kWh to spare, so the battery is full by the afternoon.